Manual

FULLTEST 3
EN - 84
Global earth resistance without tripping RCD (RA)
IN
(mA)
Display range RA
()
Resolution
()
Accuracy Overvoltage
protection
10
0 2000
1
± (3% rdg. + 1 ), 15 2000 *
CAT III 300 V
30
0.0 99.9
0.1
± (3% rdg. + 1 ), 10 2000 *
100 2000
1
100
0.0 99.9
0.1
± (3% rdg. + 3 dgt)*
100 1000
1
300
0.0 99.9
0.1
100 300
1
500
0.0 99.9
0.1
100 200
1
650
0.0 99.9
0.1
100 150
1
1000
0.0 100.0
0.1
* The accuracy may be affected unstabile mains voltage!
Test current: IN /2
Input voltage range: 100
265 V, 50/60 Hz
Nominal mains voltage : 230 or 240 V
Mains voltage U
L/PE:
Display range
(V)
Resolution
(V)
Accuracy
100 265
1 ± (3% rdg.)
Input resistance (UL/PE): 450 k
Contact voltage UC at IN:
Display range
(V)
Resolution
(V)
Accuracy
0 100 (UC LIM = 50 V)
1 ± (3% rdg. + 3 V)
0 50 (UC LIM = 25 V)