Instruction Manual
EQUITEST 5071
EN - 38
10.1. REFERENCE STANDARDS
Safety: IEC/EN61010-1, IEC/EN61557-1, -3, -4, -7
Insulation: double insulation
Pollution level: 2
Measurement category: CAT II 600VAC (inputs) / 350VAC to earth
CAT III 600VAC (inputs) / 300VAC to earth
LOW (200mA): IEC/EN61557-4
LOW
10A: IEC/EN60439-1
LOW
10AE60204: IEC/EN60204-1:2006
LOOP P-P, P-N, P-PE, Ra: IEC/EN61557-3
PHASE SEQUENCE: IEC/EN61557-7
10.2. GENERAL CHARACTERISTICS
Mechanical characteristics
Size (L x W x H): 225 x 165 x 105mm ; (9 x 6 x 4in)
Weight (batteries included): 1.7kg (35lv)
Power supply
Internal power supply: 6x1.5V alkaline batteries type AA LR6 AM3
Battery life: LOW: >80 test;
LOOP:>1000test; Ra :>1000 test;
PHASE SEQUENCE: > 1000 test
External power supply: 230V / 50/60Hz (only for continuity test with 10A)
Display
Characteristics: Dot matrix graphic module, backlit
Resolution 128x128pxl
Visible area 73mmx73mm ; (3 x 3in)
Memory:
Memory 2MByte (non-expandable)
Verification tests max 999 measurements
Interface: Serial port RS232, opto-isolated
10.3. ENVIRONMENTAL CONDITIONS
Reference temperature 23°
5°C ; (73° 41°C)
Operating temperature 0° 40°C ; (32° 104°F)
Operating relative humidity < 80%RH
Storage temperature -10 60°C; (14° 140°F)
Storage humidity < 80%RH
Max operating altitude: 2000m (6562ft)
10.4. ACCESSORIES
See the attached packing list.