Instructions
ENGLISH HP30D1
Copyright HT ITALIA 2011 Release 1.00 - 14/07/2011
USER MANUAL
SAFETY WARNING
• This note must be read in full. Any operations on live conductors can be dangerous
•
The operator is expected to be fully aware of all necessary electrical safety regulations and procedures. Safe
operation is this responsibility
• Never exceed the limit of voltage (600V) or current (1000A AC/DC) indicate in this manual
• When measuring current, if strong current nears to the clamp jaw, it will affect the accuracy
• While measuring current, always put the tested conductor in the center of clamp jaw so as to obtain a more
accurate reading
• It is up to the user to ensure that the equipment is at all times in its original safe conditions
•
Strong vibrations and impacts may cause damage to the instrument
INSTRUMENT DESCRIPTION
BATTERY REPLACEMENT
Fig. 1: Instrument description
LEGEND:
1.
Arrow which shows the
current reference
direction
2.
ZERO adjustment
thumbwheel
3. Red LED indicator
4.
ON/OFF and battery
test selector
5.
Indicate the limits of
safe area for handling
the clamp
Fig. 2: Battery replacement operation
Consider the herewith steps to replace internal
battery (for voltage <6V) (see Fig. 2):
1. Perform a little pressure on the hole on the
top of battery cover by using e.g. a small
screwdriver
2. Shift and detach the battery cover
3. Remove the battery and replace with a same
type new one considering the correct polarity
which is shown on clamp handle
4. Replace with a click the battery cover
TECHNICAL SPECIFICATIONS (ambient temperature 18°C ± 5°C and condutctor centered in the torus)
Primary rates current:
1000A AC/DC FS
Pollution degree:
2 comply with IEC/EN61010-1
Measuring range:
10A ÷ 1000A
Insulation:
Double insulation
Output ratio:
1000/1 1mV =1A
Overvoltage category:
CAT III 600V
Accuracy:
±(10%rdg+ 2mV) from 10 to 100A
±(2%rdg + 2mV) from 100 to 700A
±(1.5%rdg + 2mV) from 700 to 1000A
Power supply:
1 x 9V battery type 6LR61
Battery life:
about 72 hours
Protection index::
IP20
Position cable sensitivity: 0,5% at 50Hz
Temperature range:
-5°C ÷ +50°C
Max diameter of cable (mm):
83 (bars 100x64 or 122x54)
Temperature Coefficient:
0.1% of reading / 1°C
Dimensioni (mm):
336(L) x 137(La) x 42(H)
Load impedance:
>10kΩ e <100pF
Weight:
Ca 1.8kg
Frequency range:
DC ÷ 1000Hz
Output connector:
Hypertac connector
MEASUREMENT PROCEDURE
1. Connect clamp’s output terminal to the inputs of the instrument to be used as indicator
2. Press and hold the ON/OFF selector on “Test” position for 10s and verify the red LED on. Replace the battery (see Fig. 2) if the
red LED is off. In the event that the LED is turned on for less than 10s are not guaranteed 72 hours of operation
3. Power on the meter by move the selector on “On” position. The red LED should be fixed on. Verify the zero at display of
instrument to be used as indicator. If no move ZERO regulation trimmer on clamp before start the measurement
4. Open the clamp and put the tested conductor in the center of the clamp jaws. No gap is allowed between the connections of
clamp jaws. Always consider the correct connection of clamp (see Fig. 1)
5. Read the current value in the indicator’s display. Turn off the meter at the end of measurements
CAUTION: this symbol indicates that equipment and its accessories shall be subject to a separate
collection and correct disposal
2