Instructions
VEGA 78 /PQA823 / PQA824
- 83 -
DEFAULT CONFIGURATION (Standard-Konfiguration)
HAUPTMENÜ
PARAMETER
EINSTELLUNGEN
Analysator-
Einstellungen
System
Vierleiter
Freq[Hz]
50
Clamp Type
FLEX
FS Clamp[A]
3000
VT Ratio
1
Analysator-
Einstellungen –
Erweitert
Zoom Graphics
AUTO
Harm. Type
ALL
Harm. Values
ABSOLUTES
Zoom 1st Harm.
YES
Average Values
NO
Messeinstellungen
Comments
DEFAULT
Start
Manu
Stop
Manu
Integration period
15min
Cogeneration
OFF
General Parameter
V1N,V2N,V3N,VN-PE,V12,V23,V31,
I1, I2, I3, IN (nur PQA82x), Hz
Pt, P1,P2,P3, Qti, Qi1, Qi2, Qi3, Qtc, Qc1,
Qc2, Qc3, St, S1, S2, S3, Pft, Pft1, Pft2, Pft3,
Cosphit, Cosphi1, Cosphi2, Cosphi3, Eat, Ea1,
Ea2, Ea3, Erit, Eri1, Eri2, Eri3, Erct, Erc1,
Erc2, Erc3
Voltage harmonics
THD, DC, h1, h2, h3…h11
Current harmonics
THD, DC, h1, h2, h3…h11
Voltage anomalies
ON
Ref. Voltage anomalies
230V
Up threshold anomalies
+6%
Down threshold anomalies
-10%
Inrush current (nur PQA82x)
OFF
Flicker
OFF
Unbalance
ON
Spikes (nur PQA824)
ON (150V)
Tafel 12: Parameter bei of default configuration ( Grundeinstellung)
ACHTUNG
Die DEFAULT-Konfiguration definiert die vom Hersteller für das Messgerät
gewählten Parameter, wie in Tafel 12 dargestellt. Jede vom Benutzer im
Untermenü „Analyzer Settings” durchgeführte und gespeicherte Modifi-
kation ersetzt diese Konfiguration durch eine neue Auswahl, die sich von