Line Interactive Tower Uninterruptible Power Systems
Table Of Contents
QuickSpecs
HPE Tower UPSs
Tower UPS Specifications
Page 7
Towers G5 UPS Specifications
Electrical Input
Voltage Range
NA/JP Models = 93V – 147V
INTL Models = 168V – 286V
See Model Matrix for nominal and user selectable voltage settings.
Frequency
50/60 Hz
Online Efficiency
>95%
Electrical Output
On battery Regulation
±6%, -10% of nominal voltage
Online Regulation
NA/JP Models =
-15% to +10% of nominal voltage
INTL Models = -20% to +15% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Selection Matrix
Output protection
Firmware overload sensing and control
Battery
Type
Maintenance-free, rechargeable, valve regulated lead-acid batteries
Extended Batteries
N/A
Backup Time
See Backup Times Chart
Recharge Time
<4 hours to charge 90% usable capacity. <24 hours for complete
recharge
Voltage
750 and 1000 models are 24 volt, 1500 model is 36 volt
Communications
Serial Ports
RS232 (via RJ45 connector to DB9) and USB ports (ships with
communication cables)
Option Slot
Yes, for the UPS management card
Option Cards
Optional Network Management Card available
LCD Interface
LCD Display and Button Interface on front panel
Management Software
Power Management including HPE Power Protector software. See
HPE Power Protector QuickSpec for more information.
Environmental and Safety
Operating Temperature
0°C to 40°C (32°F to 104°F )
Non-operating
Temperature
-15°C to 40°C (5°F to 104°F) (with battery)
-15°C to 50°C (5°F to 122°F) (without battery)
Operating Humidity
0% to 90% (non-condensing)
Storage Humidity
5% to 90% (non-condensing)
Operating Altitude
Up to 1500 m above sea level
Audible Noise
<40dB in normal operation. <45dB while charging, on inverter, or in
Buck/Boost mode
Safety Markings
NA/JPN: UL/cUL, ICES B,NOM,VCCI, Int'l: CE,TUV GS,C-tick,EAC,KC
Safety Certifications
UL1778, UL60950-1; CSA22.2 No.107.3-05,; EN609501-,
EN62040-1 IEC62040-1-1, IEC 60950-1
EMC Markings
FCC-A; CISPR 22; VCCI A; CE, BSMI, C-TICK
Emissions
FCC CFR 47, Part 15 Class A, EN50091-2
Immunity
EN 55024; EN 50091-2 consisting of IEC 61000-4-2 thru IEC
61000-4-6; IEC 61000-4-11
Surge Suppression
Conforms to IEEE 587B and ANSI C62.41
RPO/ROO
The Normally Closed (NC) RPO shuts off power to all UPS
outlets when opened. The UPS must be manually restarted