Page 13
HPE R1500 G5 UPS
Electrical Input
Voltage Range
± 15% of nominal 100 and 120V models and ± 20% of nominal on
230V models. See Model Matrix for nominal and user
selectable
voltage settings via LCD Front Display Panel
Frequency
50/60 Hz ± 5Hz (auto sensing at default voltage )
Online Efficiency
92%
Electrical Output
Online Regulation
-10% to +6% of nominal voltage*
On battery Regulation
-10% / + 6% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Matrix; divided into 3 Groups
Output Protection
Firmware overload sensing and control
Battery
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Backup Time
See Backup Times Chart
Recharge Time
<3 hours to 90% usable capacity; <24 hours for complete recharge
Voltage
36V Battery String
Communications
Ports
Standard DB-9 port (Kit ships with cable for communication )
USB port (Kit ships with cable for communication)
Option Slot
(1) ( reserved for Optional Network Management Module)
Option Cards
HPE UPS Network Management Module (sold separately)
LCD Indicators
LED display integrated into the front panel
Management Software
Power Management including HPE Power Protector software. See
HPE Power Protector QuickSpec
for more information.
Environmental and Safety
Operating Temperature
32° to 104° F (0° to 40° C) ( with battery)
Non-operating
Temperature
-15° to 1122° F (-26° to 50° C)
Operating Humidity
0% to 90% (non-condensing)
Storage Humidity
0% to 90% (non-condensing)
Operating Altitude
up to 2000 meters above sea level
Audible Noise
<40db (at 1m from surface of unit) <45dBA on battery operation
Safety Markings
UL/cUL CE, TUV, C-tick, CES, EAC, VCCI, GS, KC, EK, BSMI, TIS, BIS
Safety Certifications
UL1778; UL60950, CSA22.2 No.107.1,No.107.3,; CB Bulletin
IEC62040
-1; IEC 60950-1; EN60950-1;EN 62040-1; EN 61000-3-
2+A1 +A2; EN 61000-3-3
EMC Markings
FCC-BCISPR 22; VCCI B; CE, BSMI, C-TICK
Emissions
FCC CFR 47, Part 15 Class A, EN50091-2
Immunity
EN 55024; EN 50091-2 consisting of IEC 61000-4-2 thru IEC
61000-4-6 ; IEC 61000-4-11
Surge Suppression
Conforms to IEEE 587B and ANSI C62.41
RPO/ROO Port
The Normally Closed (NC) RPO shuts off power to all UPS outlets
when opened. The UPS must be manually restarted once the
terminals are closed again. There is a preinstalled jumper in the RPO
terminals.
The Normally Open (NO) ROO initiates a UPS Power On f
unction
when closed. Opening the terminals again will shut off the UPS.
Unit Dimensions (LxWxH)
21.8x 17.2x 1.69 in (554 x 438 x 43 mm)
Shipping Dimensions
30.71x 22.8 x6.1 in (780 x 580 x 155 mm)
Unit Weight
39.06 lb (19.72 kg)
Shipping Weight
54.45 lb (24.7 kg)