ProLiant DL380 Gen10 Carrier Grade Server

QuickSpecs
HPE ProLiant DL380 Gen10 Carrier Grade Supplement
Technical Specifications
Page 11
System Unit
Dimensions
8.73 x 44.54 x 67.94 cm
3.44 x 17.54 x 26.75 in
SFF Drives:
Weight (approximate)
Maximum:
19.5 kg
43.00 lbs
Minimum: 8 SFF chassis with 1x SFF HDD and 7 HDD blanks, 2x Drive
Bay blanks,
1x processor including standard heatsink, 1x power supply
(plus blank), 1x Smart Array, 1x Riser installed
, cables for the above)
Minimum:
14.9 kg
32.75 lbs
Input Requirements
(per power supply)
Rated Line Voltage
100 to 120 VAC
200 to 240 VAC
BTU Rating
Maximum
For 800W Power Supply: 3207 BTU/hr (at 100 VAC), 3071 BTU/hr (at
200 VAC), 3112 BTU/hr (at 240 VAC) for China Only
Power Supply Output
(per power supply)
Rated Steady-State Power
For 800W Power Supply: 800W (at 100 VAC), 800W (at 240 VAC),
800W (at 240 VDC) input for China only
For 800W DC Power Supply: 800W (at
-40 VDC), 800W (at -48 VDC),
800W (at -72 VDC)
System Inlet Temperature
Standard Operating
Temperature
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C
per every 305 m (1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct sustained sunlight.
Maximum rate of change is 20°C/hr (36°F/hr). The upper limit and rate
of change m
ay be limited by the type and number of options installed.
System performance during standard operating support may be
reduced if operating with a fan fault or above 30°C (86°F).
Extended Ambient
Operating Temperature
For approved hardware configurations, the supported system inlet
range is extended to be: 5° to 10°C (41° to 50°F) and 35° to 40°C (95°
to 104°F) at sea level with an altitude derating of 1.0°C per every 175
m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of
3050
m (10,000 ft). The approved hardware configurations for this
system are listed at the URL:
http://www.hpe.com/servers/ashrae
For approved hardware configurations, the supported system inlet
range is extend
ed to be: 40° to 45°C (104° to 113°F) at sea level with
an altitude derating of 1.0°C per every 125 m (1.8°F per every 410 ft)
above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft). The
approved hardware configurations for this system are listed at the
URL:
http://www.hpe.com/servers/ashrae
GR
-63-CORE, Section 4.1.2: Shelf Level Operating Temperature and
Humidity
ETSI EN 300 019
-2-3: Stationary Use at Weather Protected Locations,
Class 3.1E
System performance may be reduced if operating in the extended
ambient operating range or with a fan fault.
Non-operating
GR-63-CORE, Section 4.1.1, Transportation and Storage Environment