User Manual
QuickSpecs
HPE Line Interactive Single Phase UPS
Tower UPS Specifications
Page 4
Towers G4 UPS Specifications
Battery Type
12 V, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a 3-5
year service life at 25C (77F).
Electrical Input
Voltage Range
± 20% for nominal voltages of 100, 110, 120, 220, 230, and
240VAC. NOTE: Nominal voltages to coincide with standard
power ranges.
Frequency
50/60 Hz
Online Efficiency
>94%
REPO
N/A
Online Regulation
-10% to +6% of nominal voltage
Electrical Output
On battery Regulation
±5%, -10% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Selection Matrix
Output protection
Firmware overload sensing and control
Battery
Extended Batteries
N/A
Backup Time
See Backup Times Chart
Recharge Time
<4 hours to charge 90% usable capacity. <24 hours for complete
recharge
Communications
Serial Ports
RS232 (via RJ45 connector to DB9) and USB ports (ships with
communication cables)
Option Slot
N/A
Option Cards
N/A
LCD Interface
LCD Display and Button Interface
Software
HPE Power Protector management software available via
download
Environmental and Safety
Operating Temperature
32° to 104° F (0° to 40° C) ( with battery)
Non-operating
Temperature
-15° to 55° F (-26° to 13° C) (without battery)
Operating Humidity
5% to 90% (non-condensing)
Storage Humidity
5% to 90% (non-condensing)
Operating Altitude
Up to 1500 m above sea level
Audible Noise
<40dB in normal operation. <45dB while on inverter
Safety Markings
NA/JPN: UL/cUL, ICES B,NOM,VCCI, Int'l: CE,TUV GS,C-tick,EAC,KC
Safety Certifications
UL1778, UL60950-1; CSA22.2 No.107.3-05,; EN609501-,
EN62040-1 IEC62040-1-1, IEC 60950-1
REPO Port
N/A
HPE T750 G4 UPS Specifications
See model matrix for other specifications.
T750 G4, NA/JP
J2P85A
Load Segments
1
Unit Dimensions (WxDxH)
5.9 x 13.4 x 8.3 inch (150 x 340 x 210 mm)
Shipping Dimensions(LxWxH)
18.7x 9.4 x 12.1 inch (476 x 238 x 308 mm)