User Manual

QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
1. Escape Button 1.
Load segment 1 circuit breaker (controls L6-30R
receptacle Item 3)
2.
Scroll up button
2.
Load segment 2 circuit breaker (controls L6-30R
receptacle Item 15)
3.
Scroll down button
3.
Large output NEMA L6-30R receptacle or IEC-60309
32A receptacle on short cords associated with load
4.
Enter/Select button
4.
Cord retention clip attachment locations
5.
Power button
5.
Load segment 1 circuit breaker (controls the C19
receptacles, but does not control the large output
6.
3 x IEC C19 receptacles on load segment 1
7.
HPE UPS Network Module
8.
Input power line cord with NEMA CS8265C plug or
IEC-309- 32A plug
9.
Ground bonding screw
10.
Serial communications port
11.
USB communications port
12.
REPO port
13.
3 x IEC C19 receptacles on load segment 2
14.
Load segment 2 circuit breaker (controls the C19
receptacles, but does not control the large output
receptacle)
Ultra-Dense Rack UPS Models Scale from Small to Enterprise IT Environments
Key Features
Front panel LCD display
Enhanced system flexibility with two independently controlled load segments
Specifications
HPE R1500 G4 UPS
Electrical Input
Voltage Range
± 15% of nominal100 and 120V models and ± 20% of nominal on
230V models. See Model Matrix
for nominal and user selectable
voltage settings via LCD Front Display Panel
Frequency
50/60 Hz ± 5Hz (auto sensing at default voltage )
Online Efficiency
92%
Electrical Output
Online Regulation
-10% to +6% of nominal voltage*
On battery Regulation
-10% / + 6%of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Matrix; divided into3 Load Segments
Output Protection
Firmware overload sensing and control,
Battery
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Backup Time
See Backup Times Chart
Recharge Time
<3 hours to 90% usable capacity; <24 hours for complete recharge
Voltage
36V Battery String
Communications
Ports
Standard DB-9 port (Kit ships with cable for communication )
USB port (Kit ships with cable for communication)
Option Slot
One ( for Optional Communication Card)
Option Cards
HPE UPS Network Module (Not included in Kit but orderable Option)
LED Indicators
LED display integrated into the front panel
Software
HPE Power Protector management software available via download
Environmental and Safety
Operating Temperature
32° to 104° F (0° to 40° C) ( with battery)