Estimated Backup Times
Page 25
Rack/Tower UPS Models
Load (Percent*)
Estimates
battery
runtime
With One
Extended
Runtime
Module
(Minutes)
With Two
Extended
Runtime
Modules
(Minutes)
With Three
Extended
Runtime
Modules
(Minutes)
With Four
Extended
Runtime
Modules
(Minutes)
(Minutes)
R/T2200 G4 UPS
384W 20% 45 142 256 346 448
960W 50% 15 55 99 110 144
1536W 80% 7 34 60 53 78
1920W 100%
5 26 47 36 57
R/T3000 G4 Low Voltage UPS
540W 20% 40 125 225 349 452
1350W 50% 12 50 99 107 140
2160W 80% 6 30 60 67 88
2700W 100% 4 24 47 52 68
R/T3000 G4 High Voltage UPS
540W 20% 45 142 256 321 417
1350W 50% 15 55 99 115 152
2160W 80% 7 34 60 72 95
2700W 100% 5 26 47 60 79
Environment-friendly
Products and Approach
End-of-life Management
and Recycling
Hewlett Packard Enterprise offers end-of-life product return, trade-in, and
recycling programs, in many geographic areas, for our products. Products
returned to Hewlett Packard Enterprise will be recycled, recovered or
disposed of in a responsible manner.
http://www8.hp.com/us/en/hpe/hp-
information/livingprogress/environmentalprogress/product-
recycling.html#.V-lPA_krKiM
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the
Hewlett Packard Enterprise web site. These instructions may be used by
recyclers and other WEEE treatment facilities as well as Hewlett Packard
Enterprise OEM customers who integrate and re-sell Hewlett Packard
Enterprise equipment.
http://www8.hp.com/us/en/hpe/hp-
information/livingprogress/environmentalprogress/product-
recycling.html#.V-lPA_krKiM