User Manual
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 23
R/T3000 G4 UPS Low Voltage
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
270W (10%)
61
281
475
665
860
540W (20%)
28
127
219
311
405
810W (30%)
17
79
140
200
260
1080W (40%)
12
57
101
146
190
1350W (50%)
10
44
79
114
149
1620W (60%)
8
36
65
93
122
1890W (70%)
7
30
54
79
104
2160W (80%)
6
26
47
68
90
2430W (90%)
5
22
41
60
79
2700W (100%)
4
20
37
53
70
R5000 UPS
Load
(Percent*)
With internal batteries
(Minutes)
With One ERM (Minutes)
With Four ERMs (Minutes)
450W (10%)
87
206
755
900W (20%)
36
99
349
1350W (30%)
22
64
222
1800W (40%)
15
47
162
2250W (50%)
12
37
126
2700W (60%)
9
31
103
3150W (70%)
8
26
87
3600W (80%)
6
23
75
4050W (90%)
6
20
66
4500W (100%)
5
18
58
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
R7000 UPS INTL
Load
(Percent*)
With internal batteries
(Minutes)
With One ERM (Minutes)
With Four ERMs (Minutes)
650W (10%)
185
282
834
1300W (20%)
62
118
357
1950W (30%)
33
70
218
2600W (40%)
21
49
153
3250W (50%)
15
37
117
3900W (60%)
11
29
93
4550W (70%)
9
24
77
5200W (80%)
7
20
66
5850W (90%)
6
18
57
6500W (100%)
5
15
50