User Manual

QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Load
(Percent)
Load
(Watts)
Minutes of Back up time
10%
109W
97
20%
219W
39
30%
328W
23
40%
438W
16
50%
547W
12
60%
656W
10
70%
766W
8
80%
875W
7
90%
985W
6
100%
1094W
5
Estimated Runtime with Extended Runtime Module (ERM)
R/T2200 G4 UPS
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
191W (10%)
80
287
491
725
898
382W (20%)
30
123
218
311
406
573W (30%)
17
75
135
189
255
764W (40%)
12
53
97
133
184
956W (50%)
9
40
74
101
142
1147W (60%)
7
32
60
81
115
1338W (70%)
5
27
50
67
97
1529W (80%)
4
23
43
57
83
1720W (90%)
4
20
37
49
73
1911W (100%)
3
17
33
44
64
R/T3000 G4 UPS High Voltage
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
270W (10%)
83
259
457
655
854
540W (20%)
31
122
219
317
414
810W (30%)
18
78
143
207
271
1080W (40%)
12
57
105
153
201
1350W (50%)
9
45
83
121
159
1620W (60%)
7
37
68
100
132
1890W (70%)
5
31
58
85
112
2160W (80%)
4
27
50
74
97
2430W (90%)
4
24
45
65
86
2700W (100%)
3
21
40
59
77