Estimated Backup Times
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Tower UPS Models
Load
(Percent)
Load
(Watts)
Estimated battery runtime at 100%
battery charge
(Minutes)
T750 UPS
10%
53W
68
20%
105W
37
30%
158W
21
40% 210W 16
50%
263W
15
60% 315W 10
70%
368W
9
80%
420W
7
90%
473W
7
100%
525W
6
T1000 UPS
10%
70W
65
20%
140W
32
30%
210W
21
40%
280W
16
50%
350W
12
60%
420W
10
70%
490W
9
80%
560W
8
90%
630W
7
100%
700W
6
T1500 UPS
10%
108W
80
20%
216W
36
30%
324W
23
40%
432W
16
50%
540W
13
60%
648W
10
70%
756W
9
80% 864W 7
90%
972W
7
100%
1080W
6
Rack UPS Models