HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Page 13
Storage Temperature
-15° to 55° F (-26° to 13° C) (without battery)
Humidity (Operation)
0% to 90%
Humidity (Non-operating)
0% to 90%
Operating Altitude
up to 2000 meters
Audible Noise
<40db (at 1m from surface of unit) <45dBA while on inverter
Safety Markings
UL/cUL CE, TUV, C-tick, CES, EAC, VCCI, GS, KC, EK, BSMI
Safety Certifications
UL1778; UL60950, CSA22.2 No.107.1,No.107.3,; CB Bulletin
IEC62040
-1; IEC 60950-1; EN60950-1;EN 62040-1; EN 61000-3-
2+A1 +A2; EN 61000-3-3
EMC Markings
FCC-BCISPR 22; VCCI B; CE, BSMI, C-TICK
Emissions
FCC CFR 47, Part 15 Class A, EN50091-2
Immunity
EN 55024; EN 50091-2 consisting of IEC 61000-4-2 thru IEC
61000-4-6 ; IEC 61000-4-11
Surge Suppression
Conforms to IEEE 587B and ANSI C62.41
Unit Dimensions (LxWxH)
21.8x 17.2x 1.69 in (554 x 438 x 43 mm)
Shipping Dimensions
30.71x 22.8 x6.1 in (780 x 580 x 155 mm)
Unit Weight
39.06 lb (19.72 kg)
Shipping Weight
54.45 lb (24.7 kg)
* The R1500 G4 UPS regulates the output voltage at -
10% / +6% of the selected nominal voltage. The regulation is accomplished by
bucking or boosting the input voltage. The voltage regulation operation is governed by the unit's input voltage spec of +/-20%. The
unit will regulate at -10% / +6% while within the limits set by the input spec. The unit will go to battery operation upon exceeding th
e
limits set by the input spec. The buck and boost voltage regulation operation, or AVR (Automatic Voltage Regulation), is
accomplished by adjusting output transformer tap selections via electromechanical relays. The transformer tap selection is
controlled via digital transition voltage set point values programmed in the unit's firmware. These programmed values are without
tolerance.
The unit will monitor the input voltage and accept a range of +/-3% of the selected nominal voltage as the target voltag
e to regulate
at -10% / +6%. For example, a unit configured to 120V nominal voltage will regulate at -10% / +6% for any voltage measured
between 116.4V and 123.6V. The digital transition voltage set point values will adjust accordingly to regulate to -10% / +6% of the
measured input voltage.
Transition set point voltages are subject to a hardware tolerances of +/-3% of the set point value.
R5000 3U UPS
BTU Break Down
BTU On Line
478 BT/hr
BTU On Battery
1041 BTU/hr
Battery Type
12V 27W
Electrical Input
Voltage Range
160-253V at 200/208V nominal; 176-253V at 220, 230, and
240V nominal
Frequency
50/60 Hz
Online Efficiency
94%
REPO
Remote Emergency Power-Off disables AC power to load
Online Regulation
-10% to +6% of nominal voltage
Electrical Output
On battery Regulation
±5% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Matrix; divided into 2 Load Segments
Output Protection
Re-settable circuit protectors
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Battery
Extended Batteries
Up to four ERMs supported
Backup Time
See Backup Times Chart