User Manual

QuickSpecs
Estimated Run Times
Page 11
Battery runtimes are approximate and may vary with equipment, configuration, battery age,
temperature, etc.
Tower UPS Models
Load
(Percent)
Load
(Watts)
Estimated battery runtime at 100% battery charge
(Minutes)
T750 G4 UPS
10%
53W
68
20%
105W
37
30%
158W
21
40%
210W
16
50%
263W
15
60%
315W
10
70%
368W
9
80%
420W
7
90%
473W
7
100%
525W
6
T1000 G4 UPS
10%
70W
65
20%
140W
32
30%
210W
21
40%
280W
16
50%
350W
12
60% 420W 10
70%
490W
9
80%
560W
8
90%
630W
7
100%
700W
6
T1500 G4 UPS
10%
108W
80
20%
216W
36
30%
324W
23
40%
432W
16
50%
540W
13
60%
648W
10
70%
756W
9
80%
864W
7
90%
972W
7
100%
1080W
6