Disk drive error conditions
The format of a disk drive error condition report is 0.1.en.ec,where:
0.1. identifies a disk problem.
en. identifies the affected disk drive bay number.
A direct correlation exists between the disk drive element number and the bay number.
The bays are numbered sequentially 1 through 14 from left to right.
ec is the error code.
Table 21 Disk drive error conditions
Error
condition
Severity Description Actions
0.1.en.01
Critical
Drive configuration or drive link rate
error:
The drive in bay en is either not
FC-compatible or is unable to operate
at the link rate established by the I/O
module.
1. If the drive is not
FC-compatible, replace it
with a FC-compatible drive or
adriveblank.
2. Replace the drive with a FC
drive capable of operating at
alinkrateestablishedbythe
I/O module.
0.1.en.02
Information Drive is missing from bay en. 1. If the bay is empty, install a
drive or a drive blank.
2. Reseat the drive to ensure that
it is properly installed.
3. Install a replacement drive or
drive blank.
0.1.en.03
Information Drive removed after the HP-UX software
activated the drive lock.
Unlock the drive using HP-UX
software.
0.1.en.04
Critical Loop A drive link rate incorrect.
The drive in bay en is capable
of operating at the loop link rate
established by I/O module A, but is
running at a different rate.
1. Reseat the drive to ensure that
it is properly installed.
2. Replace the drive.
0.1.en.05
Critical Loop B drive link rate incorrect.
The drive in bay en is capable
of operating at the loop link rate
established by I/O module B, but is
running at a different rate.
1. Reseat the drive to ensure that
it is properly installed.
2. Replace the drive.