Use the following table to identify PCI Hot Plug slot activity status according
to LED description.
Table 10-3
PCI Expansion Slot LEDs
Item Description OK to Open Slot Status
Power
Fault
Green = On
Amber = Off
No Power is currently applied to the slot. Do NOT
open the slot release lever. The slot is
functioning normally.
Power
Fault
Green = On
Amber = On
No Power is currently applied to this slot, but the
slot needs ATTENTION for a possible problem
with the slot, board, or driver. Do NOT open
the slot release lever. Examine the logs and
Compaq Insight Manager XE. If the expansion
board is faulty, follow these steps:
1. Use the PCI Hot Plug button or PCI utility
to remove power from the slot. The
green LED turns off.
2. Open the slot release lever. The amber
LED turns off.
3. Remove or replace the board.
4. Connect the cables to the PCI board.
5. Close the slot release lever.
6. Use the PCI Hot Plug button or PCI utility
to return power to the slot. The green
LED turns on.
Power
Fault
Green = Flashing
Amber = On or off
No The power slot is being turned off or on, which
may take several minutes. DO NOT open the
slot release lever. Press the PCI Hot Plug
button to cancel the operation.