User's Manual
Site requirements 7
• Cooling water
• Power
• Drain (optional)
Available to connect to central facility infrastructure
• BMS via BacNet protocol
• Security system
• Convenience outlet power
• Site networking connection
• Domestic water for humidifier (optional)
Transformer, switchboard, and water distribution kit locations
If you choose to purchase the kits, consider:
• Distance from the facility utilities
• Distance from the HP POD
The transformer and switchboard can be installed within 3 m (10 ft) of the HP POD during normal
installation. The transformer and switchboard can be installed over 3 m (10 ft) from the HP POD, but this
requires additional planning and costs. HP recommends installing the transformer and switchboard no
more than 30 m (98 ft) from the HP POD.
The water distribution kit can be installed within 3 m (10 ft) of the HP POD during normal installation. The
water distribution kit can be installed over 3 m (10 ft) from the HP POD, but this requires additional
planning and costs. HP recommends installing the water distribution kit no more than 30 m (98 ft) from
the HP POD.
HP POD connection locations
Callout Connection
1 Main input power junction box