User's Manual
Specifications 52
Feature Specification
Humidifier 3.79 l/hr (1 gal/hr) domestic
water from an alternate supply
source
Rack specifications
Standard HP POD racks (AN982A)
Feature Specification
U height 50U
Width 56-mm
Depth 1,000-mm
Maximum load weight 3,000 lb
International shock-mounted HP POD racks (AT052A)
Feature Specification
U height 46U
Width 56-mm
Depth 1,000-mm
Maximum load weight 2,760 lb
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
HP POD specification
Air temperature—Inlet to rack-
mounted components
Cold aisle setpoint temperature in BMS
Chilled water temperature 12°–19°C (55°–65°F)
Total rack-mounted component air
flow
Variable as required to maintain cold
aisle setpoint temperature
Chilled water flow rate
• 240 gal/min (908 l/min) without
utility module
• 280 gal/min (1,060 l/min) with
utility module
Chilled water pressure differential at
flow needed to meet thermal
specifications
5 psi max
Server heat load
• 450 kW standard HP POD
• 605 kW high density HP POD