User's Manual

Power management 35
Panels
The following panels are on the exterior of the HP POD.
Item Component Description
1 Electrical busway enclosed
circuit breaker (on page 36)
400A enclosed circuit breakers that powers the electrical
busways:
Two electrical busway panels are activated in the
standard HP POD.
Three electrical busway panels are activated in the high
density HP POD.
2 EPO panel (on page 36) Contains controls and status indicators for the EPO system
3 Fire alarm panel ("Fire alarm
control panel" on page 38)
Contains controls and status indicators for the fire alarm
system
4 ASSD panel (on page 36) Air sampling smoke detection system
5 EPO button Cuts off all power to the POD and activates the EPO alarm
lamp.
6 Security panel ("Security panel
location" on page 39)
Reserved for installing interface and power requirements for
any optional security devices installed.
7 EPMS panel ("EPMS panel"
on page 38)
Electrical power monitoring system
8 Humidifier ("Humidifier
(optional)" on page 44)*
Maintains the humidity inside the HP POD within a set range
to minimize static electricity.
9 Auxiliary Land power* Provides auxiliary power for the BMS or convenience outlets.
120V owner-provided power.
10 BMS panel (on page 36) Building Management System
11 Fan control (FC) panel ("Fan
control panel" on page 38)
Circuit breakers that control the fan units
12 House panel (on page 38) 120A electrical panel board providing auxiliary HP POD
electrical requirements
13 Junction Box Main input box for incoming electrical feeder cables
Optional component