User's Manual
Component identification 13
If any of the racks within the HP POD contain empty U space, you must use a heavy duty filler panel to
avoid compromising the integrity of the hot and cold aisle temperatures.
HP POD emergency components
External emergency components
Item Component Description
1 Fire strobe and horn Indication of a fire alarm condition within the HP POD.
2 EPO panel Contains controls and status indicators for the EPO system.
3 EPO alarm lamp (red) Activated when an EPO alarm button is pressed.
4 EPO button Pressing this button cuts off all power to the HP POD and
activates the EPO alarm lamp.
5 Fire alarm XFMR* Fire alarm transformer
6 ASSD panel Samples the air in the HP POD, monitoring smoke
7 Fire alarm control panel Contains controls and status indicators for the fire alarm system.
*Optional component