Setup and Install

Site requirements 7
Features Specifications
temperature*
Operating humidity
0% to 100% relative noncondensing
Non-operating humidity*
5 to 95% relative noncondensing
39ºC (102ºF) maximum wet bulb temperature
Operating altitude -76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude -76.2 to 9,144 m (-250 to 30,000 ft)
*For nonoperating specifications, consider the temperature of computer and IT equipment inside the HP POD.
The HP POD must be drained before it is moved to a new location.
For areas prone to freezing, take the appropriate water freeze protection precautions.
Lightning protection
If the HP POD is installed in an outdoor environment, HP recommends hiring a lightning protection
consultant to evaluate potential lightning risks and assess possible HP POD lightning protection schemes.