Service and Maintain

Periodic maintenance 68
Component to be inspected Task Frequency Capable Party
EPO System Test
EPO NON-FUNCTIONAL TEST
Mode Key Switch Test - rotate
keyed switch through all modes.
ARMED MODE - Verify:
Power Indicator - White
Armed Light - White
BYPASS MODE - Verify
Bypass Light - Green
TEST MODE - Verify:
Test Light - Amber
Press EPO button (each in
succession) and thermal trip to
verify:
Reset Light - White
Audible alarm
Visual lamp indicator
Replace light upon failure
Annually Qualified personnel
Emergency Lighting
Verify emergency lighting is
visible when all lighting is off and
the POD doors are shut.
Every 2 years Qualified personnel
Exit signs
Visually inspect exit signs for
damage. Replace as necessary.
Every 2 years Qualified personnel
Emergency egress
Personnel door emergency egress
panic bars. (Visual and
operational inspection.)
Every 2 years Qualified personnel
Access control
Component to be inspected Task Frequency Capable Party
System functional test
Visual inspection and operational
test of door access contact
switches
Annually Qualified personnel
Visual inspection and operational
test of the following:
Door access card readers
Electric strikes
Door release switches at each
personnel door and/or in
each personnel door panic
bar
Annually
Qualified personnel
Third-party components
All maintenance for third-party equipment will be defined by the manufacturer of the equipment. HP will, with
a defined and signed SOW, conduct all maintenance as identified by the original manufacturer.
Examples of external third party components that HP will conduct all manufacturer specified maintenance
with a signed SOW includes:
External UPS equipment