User Manual

Power, electrical, and controls 29
Top view shown
The HP POD 40c G2 electrical busways can be configured for non-redundant power or redundant power.
The HP POD 40c G2 can be installed as a single source 1N load by providing all required feeders from one
common power source and from common switchboards and transformers. A 2N redundancy installation is
configured by feeding the parallel power paths from independent power sources, switchboards, and
transformers.
Non-redundant power installation (1N load)All eight busways are powered from the same power
feed.