User Manual
Life safety systems 17
The EPO system must be reset before you can power up and restart the HP POD 40c G2. To reset the EPO
system:
1. Verify that the key control for the EPO mode is in the Armed position.
2. Press the white EPO Reset button.
If you triggered the EPO system manually, you must reset the EPO button that you pressed to the Active
position.
ECS touchscreen and EPO indicators
The ECS touchscreen and EPO indicators are located on the door to the control panel.
The touchscreen enables you to easily configure the environmental parameters, access data, and monitor
environmental, life safety, and security conditions within the HP POD 40c G2.
The EPO indicators provide EPO status. The EPO key control and EPO reset button enable you to adjust the
EPO system mode.
Item Component Indicator color Description
1
External EPO status
indicator
•
White—Normal operating mode
•
Yellow—EPO cover open alarm or
EPO system operating in test mode
•
Red—EPO shutdown
Indicates the operating status of the HP
POD 40c G2
2
Power on White Indicates the EPO power status
3
EPO shutdown Red Indicates an EPO shutdown or alarm
situation
4
EPO armed White Indicates that the EPO system is armed and
operational
5
EPO test mode Yellow Indicates that the EPO system is operating
in test mode or that an EPO cover is open
6
EPO bypassed Green Indicates that the EPO functionality and
shutdown is bypassed