Getting Started Guide

Supported facility connections 21
It is your responsibility to facilitate these connections. HP can make these connections when specifically
contracted to deliver these services and a Scope of Work has been drafted, reviewed, and signed for
delivery services.
The customer must provide an independent connection for each system listed in the following table.
Alarm Description
Fire prevention alarm
Smoke is detected in the HP POD 40c G2.
Fire suppression
system (optional)
The suppression system alarm is activated and gas is
dispersed to suppress a fire.
Security
A security breach occurred.
EPO
The EPO system is activated by manually pressing the
EPO button or by a thermal event, and the HP POD 40c
G2 is shut down.
The electrical layout of the fire alarm system is described in the schematic drawing that is supplied with the
HP Performance Optimized Datacenter 40c G2 Site Drawing Package.