Power, electrical, and controls 33
Feature Specification
Max power per PDU
30 A = 17 kW; 60A = 34 kW
Average capacity per rack
30 kW
Peak capacity per rack
69.12 kW
Voltage to rack
240V
Rack configuration
Redundant/Non-redundant capabilities
Lighting
The HP POD 240e NA includes lighting in each section:
IT section Afour LED lights and two emergency lights
IT section Bfour LED lights and two emergency lights
Hot aislesix LED lights and two emergency lights
Service aislefour fluorescent lights
A light switch is located at every personnel door. For more information about light switch locations, see "Life
safety component identification (on page 10)."
The IT sections and the hot aisle LED lights are tied to battery backup power, so the emergency lights will
activate to keep the interior of the HP POD 240e NA illuminated during a power outage or emergency.
For more information about lighting, see the HP Performance Optimized Datacenter 240e NA Maintenance
and Service Guide.