Environmental control system 48
The Basic System Configuration screen displays the basic alarm parameters, humidifier control, and fan
controls. The configured parameters are only used to trigger an ECS alarm. The parameters listed on this
screen do not configure the cooling system.
You can select and configure the following parameters:
Cold aisle temperature alarm
Hot aisle temperature alarm
Humidity alarm
Differential pressure alarm
Differential pressure filter alarm
Chilled water supply pressure
Chilled water supply temperature
Chilled water return temperature
Chilled water return pressure
You must select Save to store the parameter changes in the system configuration file. If you do not save your
changes, the old parameters stored in the configuration file reload when the system starts.
Configuring the chilled water supply temperature alarm parameters
The current temperature parameters appear on the related buttons.