User's Manual

Power, electrical, and controls 29
Front view shown
Feature Specification
Number of busways
2
Frequency
50-60 Hz
Amps (per busway)
200 A
Voltage (per busway)
380-415 V
Grounding
Copper
Busway conductors
3-phase + neutral + equipment ground
Panel schedules
The panel schedule for each electrical panel is permanently affixed to the inside cabinet door of each
electrical panel.
Wire color code
IMPORTANT: The use of UL-approved colored tape over another color of wire is only acceptable
on wire sizes #2 and larger.
220-240 V wiring systemPower required for the transformer in control cabinets and convenience outlet
Wire color Description
Brown
Single-phase current carrying conductor
White
Blue
Green and yellow
Equipment grounding conductor
Bonding conductor
Earth ground
380-415 V wiring systemCritical IT power feeds and main power feeds