Setup and Install

HP POD specifications 14
Item Component
7 Fan sequencers
8 Fan power relays
9 Redundant power relays
10 EPO controls and indicators
Water supply specifications
Feature Specification
Facility input temperature to HP POD 12º to 24ºC (55º to 75ºF)
Working pressure 1034 kPa (150 psi)
HP POD pressure drop 1732 kPa (25 psi)
HP POD water flow rate 454 l/min (120 gal/min)
Cooling water supply and return
connections
North America:
Two 7.62 cm (3 in.) ASME
B16.5 class 150# flanges
International:
Two DIN PN16 DN80 flanges
Humidifier
See the humidifier manual for
exact requirements