System Startup, Configuration, and Shutdown Reference Manual (32650-90892)

196 AppendixA
Using the Access Port (AP)
Configuring the Console
AP self-test detects only approximately 70 percent of the faults on the AP.
MESSAGE: SPU hardware was successfully reset. (APMSG 02)
CAUSE: This message indicates that the AP did not enter the three possible error states. It
does not mean that the AP has somehow detected that the processor has restarted or that
it was cleared, for example. The AP has no way to determine the internal state of any other
assembly in the SPU.
MESSAGE: Console terminal not set to 9600 bits per second. Console port will operate
at xxxx bits per second. (APMSG 03)
CAUSE: The AP senses the setting of the console connected to local console port using
ENQ/ACK. The console should be operating at 9600 bits per second. If it is operating at
4800, 2400, 1200, 600 or 300 bits per second, the AP senses this and operates the port at
this baud rate.
If the above message appears on the terminal screen, the AP and the terminal are both set
for the same baud rate. If the terminal is accidentally set for other than 9600, the
above-referenced procedure should be followedto reset the terminal and AP for 9600. If the
terminal is set for 9600, the AP or the terminal is defective.
MESSAGE: String was truncated to 24 characters. (APMSG 04)
CAUSE: You can enter only up to 24 displayable characters in the answer to the query on
the screen. All characters past the twenty-fourth were discarded. No action is necessary if
the resulting truncated string is acceptable as the answer to the query. If the resulting
string is not acceptable, continue command execution until you are again prompted for the
string and enter the new string.
MESSAGE: AP configuration lost. Use CA and ER commands to recover. (APMSG 05)
CAUSE: If this message recurs after each reset, power on, or self-test execution, the AP is
defective.