Management Agents Events Reference
Event DescriptionEvent SeverityEvent ID
The BPSs for the cabinet are illegally configured. Data Byte 3 = PDCA number.
Probable Cause: The BPS are installed in an illegal configuration. Recommended
Action: Re-configure the BPS in a manner consistent with the explanation in the
Problem Description statement SNMP Trap: hpevtIllegalBpsCfgOrPhaseFlt - 7824 in
HPIFPTRAP.MIB.Warning7824
BPS ID received from installed Bulk Power Supply was unknown. Probable Cause:
The designated power supply is responding with an illegal BPS ID. It could be a
faulty supply, a different revision, or a wrong supply in the wrong box. Recommended
Action: Replace this Bulk Power Supply with a proper one. SNMP Trap:
hpevtIllegalBpsid - 7825 in HPIFPTRAP.MIB.Warning7825
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature has
risen to a critical level. Recommended Action: Shutdown and power off the system.
Correct air temperature problem. SNMP Trap: hpevtInletOvertempHi - 7827 in
HPIFPTRAP.MIB.Error7827
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. SNMP Trap:
hpevtInletOvertempLo - 7828 in HPIFPTRAP.MIB.Warning7828
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. SNMP Trap:
hpevtInletOvertempMid - 7829 in HPIFPTRAP.MIB.Error7829
IO Fan Failed. Probable Cause: IO Cooling Fan Failed. Recommended Action: Replace
IO Fan Module as soon as possible following the IO Fan Module Remove and Replace
Procedures. SNMP Trap: hpevtIofanFail - 7836 in HPIFPTRAP.MIB.Warning7836
Cabinet Power System is in overload. Probable Cause: A Bulk Power Supply has
failed, or, entities were added. Look for one or more BPS_Fail Chassis Codes preceding
this one for the actual failures. This code is a warning of possible cabinet unreliability.
Recommended Action: Contact HP Support personnel to troubleshoot the problem.
SNMP Trap: hpevtPowerOverload - 7842 in HPIFPTRAP.MIB.Warning7842
Cabinet Shutdown - Insufficient Blowers. Probable Cause: One blower has failed
creating condition N. Before condition N was corrected, another blower in the same
cabinet was declared failed. This created the illegal condition of N-1. Recommended
Action: Contact HP Support personnel to troubleshoot the problem SNMP Trap:
hpevtShutdownBlowr - 7845 in HPIFPTRAP.MIB.Error7845
Cabinet Shutdown - Insufficient IO Fans. Probable Cause: One IO fan has failed
creating condition N. Before condition N was corrected, another IO fan in the same
cabinet failed. This created the illegal condition of N-1. Recommended Action: Contact
HP Support personnel to troubleshoot the problem SNMP Trap: hpevtShutdownIofan
- 7846 in HPIFPTRAP.MIB.Error7846
IO Expansion Utility Cabinet Fan Failed. Probable Cause: IO Expansion Utility Fan
or Fan sensor failure PM failure. Recommended Action: Contact HP Support personnel
to troubleshoot the problem SNMP Trap: hpevtXucFanFail - 7849 in HPIFPTRAP.MIB.Warning7849
Watchdog Timer Expired. Probable Cause: CLU has been reset after a firmware
update. Recommended Action: No action is required. SNMP Trap:
hpevtCluWatchdogReset - 7855 in HPIFPTRAP.MIB.Error7855
Platform Agent Events 43