Management Agents Events Reference
Event DescriptionEvent SeverityEvent ID
HP unsupported DIMM(s) has been detected on this partition. Probable Cause: HP
PFM service has detected one or more HP unsupported DIMMs on this partition.
Recommended Action: Make sure to have HP supported DIMMs installed. SNMP
Trap: hpevtUnSupprtDimmInPartition - 12557 in HPIFPTRAP.MIB.
Warning12557
OS run-time critical shutdown occurred. Probable Cause: The OS has caused the
system to shut down. Recommended Action: Look at OS logs and crash data to
determine why the system shut down. SNMP Trap: hpevtRuntimeCritShtDwn -
12560 in HPIFPTRAP.MIB.
Error12560
The amount of power expected to be drawn by the currently operating hardware is
greater than the rating of the currently operating Bulk Power Supplies (BPS). Probable
Cause: A bulk power supply has failed or was removed when the system had the
minimal number of required bulk power supplies. Recommended Action: Replace
the failed or removed bulk power supply. SNMP Trap: hpevtPwrExptGreatrPwrBulk
- 12586 in HPIFPTRAP.MIB.
Error12586
Bulk power supply (BPS) redundancy has been lost on one or more row(s) of power
supplies in the complex. The further loss of a single BPS or an AC grid will most
likely result in the shutdown of partitions. Probable Cause: A change has occurred
in the number of properly operating bulk power supplies installed in the system.
Recommended Action: Replace missing or failed bulk power supplies. SNMP Trap:
hpevtBulkPwrReduncLost - 12589 in HPIFPTRAP.MIB.
Error12589
AC redundancy has been lost on one or more power supplies in the complex. The
further loss of a single Bulk Power Supply (BPS) or the other AC grid will most likely
result in the shutdown of partitions. Probable Cause: An AC source has been lost.
Recommended Action: Verify that the chassis is connected to working power grid(s).
SNMP Trap: hpevtACReduncLost - 12591 in HPIFPTRAP.MIB.
Error12591
The fans that cool a region of the system are not redundant. If an additional fan fails
or is removed from this cooling domain, the partitions on this system will be shut
down to prevent damage. Probable Cause: One or more fans in the cooling domain
have been removed or are not functioning properly. Recommended Action: Removed
failed fan (if any) and insert working fan. SNMP Trap: hpevtFanCoolNotRedunc -
12593 in HPIFPTRAP.MIB.
Error12593
An insufficient number of fans are working in a cooling domain to permit system
operation. Running partitions will be shut down immediately to prevent damage
due to excessive heat. Probable Cause: More than one fan in a cooling domain have
been removed or are not functioning properly. Recommended Action: Remove failed
fan(s), if any, and insert working fans. SNMP Trap:
hpevtFanInsufficientInCoolDomain - 12595 in HPIFPTRAP.MIB.
Error12595
Operating system is not using all available processors for the current system. Probable
Cause: Operating system license doesn't allow all processors to be used, or some
processors are disabled / deconfigured. Recommended Action: Verify the correct
operating system license to be used; Verify if all processors are enabled. SNMP Trap:
hpevtOSNotUseAllProcs - 12627 in HPIFPTRAP.MIB.
Warning12627
A Fabric Message Processor (FMP) has unexpectedly reset. The system has recovered
from the problem. Probable Cause: There is a firmware problem. Recommended
Action: Verify that the most recent firmware is installed on the system. SNMP Trap:
hpevtFMPUnexpctRstHasRcv - 12863 in HPIFPTRAP.MIB.
Error12863
Foundation Agent Events
Event DescriptionEvent
Severity
Event ID
The Foundation Agents service detected an error. The insertion string is: %1. The
data contains the error code.
Warning256
The Foundation Agents service could not allocate memory. The data contains the
error code.
Warning257