Technical information
187
For the latest product & technical information, refer to the Information Sources on pages 2 and 3.
Updated 10/02/01
NETBAY RACK
POWER CONFIGURATOR
Country-Specific Considerations: Europe, Mid-East,
Africa, Asia Pacific, parts of Latin America
1. Device to Rack PDU power cable
IEC C13 to C14, 10/15a cable
typical: P/N 36L8886 (2.8m)
requirement: C14 plug, long enough to reach
available option: 94G7448 (14ft)
2. Rack PDU to wall line cord
IEC C19 to country-specific connector,
16/20a, 14ft (4.3m)
3. Rack PDU to UPS power cable
IEC C19 to C20, 16/20a
P/N 00N7700 (2m)
provided with P/N 37L6861 (APC SU-5000RMB)
4. Rack PDU to Front-end PDU power cable
IEC C19 to C20, 16/20a
P/N 00N7698 (1m)
provided with the Front-end PDUs
5. Front-end PDU to wall line cord
special to country-specific connector,
30/32a, 8.2ft (2.5m)
Power Cables:
(2) Line Cords: Rack PDUs
(5) Line Cords: Front-end PDUs
Part
Number
Plug Type
Source Circuit (single
phase 50/60Hz)
PDU Output
(single phase 50/60Hz)
37L6866
NEMA L5-20P 100-127Vac, 20a seven 100-127Vac, shared 15a
NEMA L6-20P 200-240Vac, 20a
seven 200-240Vac, shared 15a
37L6868 CEE7-VII 220-240Vac, 16a
37L6870 IEC 309-2P+Gnd 220-240Vac, 16a
37L6872 SII 32 220-240Vac, 16a
37L6874 CEI 23-16 220-240Vac, 16a
37L6876 SABS 164 220-240Vac, 16a
06P6028 BS 1363/A 220-240Vac, 13a
37L6864
country-specific line
cord provided by IBM
country specific country specific
Part
Number
Plug Type
Source Circuit (50/
60Hz)
PDU Output
(single phase 50/60Hz)
37L6883 NEMA L5-30P 100-127Vac, 30a, single-phase
three 100-127Vac, 20a each, shared
30a
37L6884 NEMA L6-30P
200-240Vac, 30a, single phase
line-to-line with ground
three 200-240Vac, shared 20a
37L6886 NEMA L21-30P
200-250Vac, 30a, three-phase
Y-connection with neutral
three 100-127Vac (115-145), 20a
each
37L6885 IEC 309-2P+Gnd 220-240Vac, 32a, single-phase
three 220-240Vac, 16a each,
shared 32a
37L6887 IEC 309-3P+N+Gnd
380-415Vac, 32a, three-phase
Y-connection with neutral
three 220-240Vac, 16a each
Power Load Capacity -- xSeries / Netfinity Rack Systems
220V
230V
235V 240V
2350W
2300W
2200W
2400W
220V
230V
235V 240V
2350W
2300W
2200W
2400W
220V
230V
235V
240V
2350W
2300W
2200W
2400W
220V
230V
235V 240V
1566W
1533W
1466W
1600W
C
C
C
C
220V
230V
235V
240V
1566W
1533W
1466W
1600W
220V
230V
235V
240V
1566W
1533W
1466W
1600W
C
C
220V
230V
235V
240V
3525W
3450W
3300W
3600W
4400W 4600W 4700 W
4800W
220V 240V
235V
230V
6600W
6900W
7050W
7200W
220V
240V
235V230V
C
@ country specific:
IEC 309-2P+G
CEE7-VII
SII 32
SABS 164
BS 1363 w/fuse
CEI 23-16
etc.
W
W
220-240Vac
1 phase
16a
220-240Vac
1 phase
32a
380-415Vac
3 phase
32a
w/neutral
various @
309-2P+G
309-3P+N+G
220V
shared 20a
NOTE:
C = Rack PDU has a 15a circuit breaker
W = FE PDU has a 20a fuse