Technical information

181
For the latest product & technical information, refer to the Information Sources on pages 2 and 3.Updated 10/02/01
IBM RACK CABINET
IBM Rack-Mounted Units
Standard Power Cords
7
Description
Machine
Type /
Model
Size
(U)
4
Approx
Weight
(lbs)
Power (Watts)
Typical/Max
(All cords to same
source)
Number of P/S
and Line Cords
Typical/Max
6ft NEMA 5-15P
P/N 6952301
9ft NEMA 5-15P
P/N 6952300
14ft NEMA 5-15P
P/N 13F9961
9ft NEMA 6-15P
P/N 1838574
9ft IEC 320-C14
P/N 36L8886
14ft IEC 320-C14
P/N 36L8861
8ft IEC 320-C20
P/N00N7701
Server System Units
x200
1
8478 4 42 245/350 1/1 1
x220
1
8645 4 42 245/350 1/1 1
x230 8658 5 79 250/357 1/1 1
x230 w/Pwr Upgrade
5
8658 5 79 315/450 1/3
5
1
x232 8668 5 76 385/550 1/1
6
1
x232 w/Pwr
Conversion
6
8668 5 80 420/600 2/3
6
2/3
x240 8664 5 80 315/ 4 50 2/3 2
x250 8665 8 123 350/475 2/4 2
x300
2
8672 1 29 14 0/ 2 00 1/1 1 1
x330
2
8654/8674 1 29 140/200 1/1 1 1
x340 8656 3 61 270 /415 1/2 1 1
x342 8669 3 62 262/375 1/2 1 1
x350 8682 4 76 365/525 1/3 1 1
x370
3
8681 8 160 1015 /1450 3/3 3 3 3
x380 8683 7 150 1400/2000 2/2 2
Storage Units
EXP300 35311RU 3 90 285/360 2/2 2
FAStT200 35421RU 3 56 275/390 2/2 2
FAStT200HA 35422RU 3 56 275/390 2/2 2
FAStT500 RAID
Controller
35521RU 4 76 140/200 2/2 2
FAStT EXP500
Storage Unit
35601RU 3 61 245/350 2/2 2
FC Switch 8-port 2109S08 1 17 -/200 1/2 1
FC Switch 16-port 2109S16 2 28 -/200 1/2 1
Tape Units
NetMEDIA 3551001 3 37 130/18 5 2/2 2
DLT Library 3502R14 4 70 -/135 1/1 1
Magstar 1 drive 3570C21 6 64 14 0 / 2 00 1/1 1 1
Magstar 2 drives 3570C22 6 64 140/200 2/2 2 2
1. Requires 4Ux20D Tower-to-Rack Kit (P/N 09N4300) to mount server unit into an EIA rack cabinet.
2. To provide adequate cooling, blank filler panel kit (P/N 94G6670) should be placed on the front of any unused rack space. If non-IBM racks are
to be used, assure that both front and rear doors offer a minimum of 48% open area uniformly distributed and in line with installed servers. A
clearance of 51 to 64mm (2 to 2.5in) must be maintained between the front of the door and the system unit’s front bezel. The rear door must
maintain the same or greater clearance. Nonrack or NetBAY3 installations are not supported.
3. x370 requires installation of extension kit (P/N 36L9703 or 36L9702) when installed in a 9306-900, 910 or 9306-200, respectively, for proper rear
door clearance.
4. 1U = 1.75in (4 4.45mm ).
5. One power supply standard; the Hot-Swap Power Supply Upgrade Kit (P/N 37L6881) allows one to three hot swap power supplies.
6. One 385W power supply standard on base models, two 250W power supplies on redundant models. xSeries Hot-Swap Power Conversion
Kit (P/N 24P3513) supports one to three hot-swap power supplies. Base models require removing the standard power supply and adding the
conversion kit with 250W power supply. Redundant models do not require adding the conversion kit.
7. Optional rack power cords: P/N 94G6667 - 14ft NEMA 5-15P; P/N 94G7448 - 14ft IEC 320-C14.
General rack placement rules and other information:
- Locate heaviest components at the bottom of the rack (i.e., UPS, then servers or storage, etc.).
- Do not extend more than one component on side rails at a time.
- Maximum of three UPSs (including no more than two APC 5000 UPSs) per rack.
- Utilize sidewall compartments for mounting PDUs and console switches prior to using EIA space.
- When mounting components in a rack, consider user and service requirements.
- When selecting length of power, console and storage cables, consider extension of cable management arms and overall cable routing.
- BTUs = Watts x 3.41.