Specifications
136
Updated
17/10/00
To access IBM information specific to your country via the World Wide Web, use address: http://www.pc.ibm.com
IBM Netfinity NetBAY3/NetBAY3E Stackable
Enclosur
e
Supported Devices NetBAY3 NetBAY3E Size (U) Weight(lb/kg) Max/Enclosure Max/Stack
Servers
Netfinity 7600
1
X - - 120/54.4 n/a 1
Netfinity 7100
X - - 120/54.4 n/a 1
Netfinity 7000-M10
2
X - - 160/72.6 n/a 1
Netfinity 5500
X - - 120/54.4 n/a 1
Netfinity 5500-Mxx
X - - 123.4/56.0 n/a 1
Netfinity 8500R
3
- X 170/77.1 n/a 1
Expansion
4
Netfinity EXP200
X X 3 80/36 1 3
Tape Units
4
NetMEDIA
X X 3 37/17 1 3
Power
4
APC Smart-UPS 1400RMiB
X X 3 55/24.9 1 1
APC Smart-UPS 3000RMiB
X X 3 112/50.8 1 1
200-240V PDU
XX1 8/3.6 1 1
Networking
4
2210 Multiprotocol Router
X X 1, 2 7/3.2, 20/9.1 3, 1 9, 3
8230 T-R Controlled Access Unit
X X 2 15/6.8 1 3
8235 Dial-in Access to LANs
XX1 8/3.6 3 9
8237 Ethernet Hub
X X 2 10/4.5 1 3
8238 Nways T-R Hub
X X 2 11/5.0 1 3
8271 Ethernet Switch
X X 2 16/7.3 1 3
8272 T-R Switch
X X 2 16/7.3 1 3
8285 ATM Switch
X X 3 70/31.8 1 3
1. Netfinity 7600 systems are rack mountable and ship without a keyboard or mouse. In order to be utilised with a NetBAY3 or in a tower configuration, optional 8Ux28D Rack-to-Tower Kit
(P/N 28L4705) must be installed.
2. Netfinity 7000-M10 systems are rack mountable and ship without a keyboard. In order to be utilized with a NetBAY3 or in a tower configuration, optional Rack-to-Tower Conversion Kit
(P/N 01K8005) must be installed.
3. Netfinity 8500R systems are rack mountable and ship without a keyboard. In order to be utilized with a NetBAY3E or in a tower configuration, optional Rack-to-Tower Kit (P/N 28L4705)
must be installed.
4. NetBAY3 and NetBAY3E do not contain a top cover and therefore require a supported server as the top component in a stack
Installation Guidelines:
1) Locate power units with line cords in the bottom enclosure.
2) Install components starting from the bottom; start with the heaviest device.
3) If nothing is installed in the enclosure, attach the rear blank panel for stability.
UPS
EXP200
Networking
Netfinity 7600
Sample
Configuration
19 in x 24 in.
483 mm x 610mm
3.2 ft
2
36 in.
19 in.
26 in.
6 in.
152 mm
Front
Service clearance
Operational clearance
(1.7 ft.X 3 ft.= 5 ft.
2
)
(508 mm x 914 mm = 0.46 m
2
)
36 in.
36 in.
914 mm
36 in.
6 in.
36 in.
914 mm
20 in.
508 mm
36 in.
914 mm
(7.6 ft. X 8.2 ft.= 62.3ft
2
)
(2316 mm x 2499 mm = 5.79 m
2
)
NetBAY3