Specifications
2 General site preparation guidelines
The HP Integrity BL860c i2 Server Blade does not have cooling or power systems. Cooling and
power is provided by the c-Class enclosure.
Enclosure environmental specifications
NOTE: This information is for both c3000 and c7000 Enclosures.
ValueSpecification
Temperature range*
10°C to 35°C (50°F to 95°F)Operating
-30°C to 60°C (-22°F to 140°F)Non-operating
Wet bulb temperature
28ºC (82.4ºF)Operating
38.7ºC (101.7ºF)Non-operating
Relative humidity (noncondensing)**
20% to 80%Operating
5% to 95%Non-operating
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m (1.8°F
per 1000 ft) to 3048 m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit
is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3
KPa/4.4 psia.
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F).
Altitude maximum for storage corresponds to a pressure minimum of 70 KPa.
For more information on the c-Class enclosures, go to http://h71028.www7.hp.com/enterprise/
cache/316735-0-0-0-121.htmlf.
For more site preparation information, go to http://www.hp.com/go/Blades-docs , select HP
Integrity BL860c i2 Server Blade in the list of servers, and then select the Generalized Site
Preparation Guidelines.