HP StorageWorks XP20000 Disk Array Site Preparation Guide (AE190-96002, September 2007)
3Electricalspecifications
The detailed electrical specifications in this chapter are p rovided to help your site electrician perform
any necessar y electrical work related to site prep.
AC line voltag
erequirements
The AC power re
quirements are essentially the same for both the primary and the second racks. Each
rack o p erates on 200 VAC nomina l, 20 amps, 50 or 60 H z, s ing le-phase power. An independent
branch circuitandacircuit breakerare required foreachACinput power cord.
Thefollowing tablelists specific power requirements.
Parameter
200 VAC 208 VAC 220 VAC 230 VAC 240 VAC
Minimum operating voltage (VAC)
184 191 202 212 221
Maximum operating voltage (VAC)
212 220 233 244 254
Rated line current per power cord
16A 16A 16A 16A 16A
Number of power cords
4 4 4 4 4
Recommended circuit b reakers
20A 20A 20A 20A 20A
Number of circuit breakers
4 4 4 4 4
Important n
otes:
208VAC is 60 Hz only. 220 VACand 240VAC are50 Hzonly. Ratedlinecurrent perpower cord is
the
maximum allowable current under worst case conditions. This value applies to each individual power
cord and is
specified in RMS amperes. For the second rack, four power cords and circuit breakers are
strongly recommended even though a minimum config uration containing only one expansion disk chassis
requires only t wo power cords and two circuit breakers. If a second expansion disk chassis is added to
the
second rack, four power cords and four circuit breakers a re required.
AC inputs
The disk array primary rack has four separate connections to 200 VAC, single-phase, 20-amp power.
The AC power inputs to the primary rack are distributed to four power distribution units (PDUs) as shown
in the
following figures. This provides fault tolerant operation of the disk array. Each pair of AC inputs
must be capable of supporting the entire current demand for the cabinet. Each PDU is fitted with an
IEC320-C20 inlet that fits the supplied input power cord.
XP20000 Disk Array Site Preparation Guide
33