HP StorageWorks XP24000 Disk Array Site Preparation Guide, v01 (AE131-96002, June 2007)
Table 15 Humidity specifications
Noncondensing relative humidity (RH)Humidity range type
50% to 55%Recommended operating humidity range
at 22 degrees C (71 degrees F)
20% to 80%Operating humidity range
at 22 degrees C (71 degrees F)
8% to 90%Nonoperating humidity range
5% to 95%Shipping and storage humidity range
(product packed in factory packing)
26 degrees C, 79 degrees FOperating maximum wet bulb temperature
27 degrees C, 81 degrees FNonoperating maximum wet bulb temperature
29 degrees C, 84 degrees FShipping and storage maximum wet bulb temperature
Vibration specifications
Continuous vibration can cause a slow degradation of mechanical parts and, when severe, can cause
data errors in disk drives. Mechanical connections such as printed circuit assembly (PCA) conductors,
cable connectors, and processor backplane wiring can also be affected by vibrations. Vibration
specifications apply to all three axes. For specification tests, see ASTM D999-91 Standard Methods
for Vibration Testing of Shipping Containers.
Table 16 Vibration specifications
SpecificationCondition
0.25 mm, 5–10 Hz
0.05 G, 10–300 Hz
Operating
2.5 mm, 5–10 Hz
0.5 G, 10–70 Hz
0.05 mm, 70–99 Hz
1.0 G, 99–300 Hz
Nonoperating
0.5 G, 15 min. (at four most severe resonances
between 5 and 200 Hz)
Shipping and storage
(product packed in factory packing)
Shock specifications
The following table lists shock specifications. For horizontal shock testing methods, see ASTM D5277-92
Standard Test Methods for Performing Programmed Horizontal Impacts Using an Inclined Impact
Tester. For vertical shock testing methods, see ASTM D6055-96 Standard Test Methods for Mechanical
Handling of Unitized Loads and Large Shipping Cases and Crates.
XP24000 Disk Array Site Preparation Guide 35