HP StorageWorks XP24000 Disk Array Site Preparation Guide, v01 (AE131-96002, June 2007)
CAUTION:
If your computer room has carpeting, place static discharge mats so that personnel must walk across them
before touching any part of the array. Failure to comply with this precaution can result in equipment
damage through static discharge.
Floor cutouts
The following figures show the locations of floor cutouts under the DKC and DKU for cabling. Position
floor cutouts toward the center of the cabinet. The position may be off-center as long as the cutout is
within the allowable range and allows smooth entrance of external cables. Be sure to check the
relationship between the position of the cutout and the opening on the bottom of the cabinet, since
they must align.
XP24000 Disk Array Site Preparation Guide 25