HP StorageWorks XP24000 Disk Array Site Preparation Guide, v01 (AE131-96002, June 2007)
30-amp, 50 or 60 Hz, three-phase DKU
Table 28 DKU power specifications, 30-amp, 50 or 60 Hz, three-phase
415
VAC
50 Hz
only
400
VAC
50 Hz
only
380
VAC
50 Hz
only
240
VAC
50 Hz
only
230
VAC
50 or
60 Hz
220
VAC
50 Hz
only
208
VAC
60 Hz
only
200
VAC
50 or
60 Hz
Parameter
382368350221212202191184Minimum
operating
voltage
(VAC)
440424403254244233220212Maximum
operating
voltage
(VAC)
4.965.155.428.588.949.399.1210.3Rated line
current per
power cord
(Amps rms)
22222222Number of
power cords
3030303030303030Recommended
circuit breakers
(amps)
22222222Number of
circuit breakers
Receptacle part numbers and ordering information
The following table lists the plug and receptacle part numbers for 60 Hz configurations of the HP
XP24000 disk array.
Table 29 Receptacle part numbers
ReceptaclePlugBreaker ratingPower source
Russellstoll or Thomas &
Betts 3933 (alt. 9C33U0)
or 3753 (alt. 9R33U0W)
Russellstoll or Thomas &
Betts 3750DP
30 ASingle-phase
Russellstoll or Thomas &
Betts 9C53U2 or
9R53U2W
Russellstoll or Thomas &
Betts 9P53U2
50 A
Russellstoll 3934 (alt.
9C34U0) or 3754 (alt.
9R34U0W)
Russellstoll 3760PDG or
DDK 115J-AP8508
30 AThree-phase