HP XP P9500 Site Preparation Guide (AV400-96609, January 2014)
Table 16 Floor load rating and required clearances for a two rack configuration (two DKC)
(continued)
Required Clearance (a+b) mFloor Load
Rating
(kg/m2)
Clearance (c) m
C=0.6C=0.6C=0.4C=0.2C=0
0.81.01.21.31.5300
Notes:
1. Actual clearances for installation should be determined after consulting with construction specialist responsible for
installation building, as they could vary depending on the size/layout of the system and building conditions.
2. When various configurations of disk arrays are arranged in a row, clearance values based on the largest disk array
configuration should be used.
3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible.
Three rack configuration (left module)
The following figure and table shows the service clearances and floor load rating for a three-rack
configuration.
Figure 7 Service clearances for a three rack system (left module)
*1 Clearance (a+b) is based on the floor load rating and the clearance (c). Floor load rating and
required clearances are shown in Table 17 (page 28).
*2 Clearance (d) is required over 300mm to open the front door. In the case that the clearance
(d) is less tan the clearance (a), give priority to clearance (a).
Service clearance, floor cutout, and floor load rating 27