HP XP P9500 Site Preparation Guide (AV400-96609, January 2014)
Figure 6 Service clearances for a two rack system (two DKC)
*1 Clearance (a+b) is based on the floor load rating and the clearance (c). Floor load rating and
required clearances are shown in Table 16 (page 26).
*2 Clearance (d) is required over 300mm to open the front door. In the case that the clearance
(d) is less tan the clearance (a), give priority to clearance (a).
*3 Clearance (e) is required over 200mm to open the rear door. If clearance (e) is less than
clearance (b), give priority to clearance (b).
Table 16 Floor load rating and required clearances for a two rack configuration (two DKC)
Required Clearance (a+b) mFloor Load
Rating
Clearance (c) m
(kg/m2)
C=0.6C=0.6C=0.4C=0.2C=0
00000.1500
000.10.20.3450
00.20.30.40.5400
0.30.50.60.80.9350
26 Installation requirements