HP XC System Software Release Notes for Version 3.1
Table 3-3 iLO Settings for HP ProLiant DL585 G2 Nodes
Set To This ValueOption NameSubMenu NameMenu Name
Create a common iLO user name and password for every
node in the hardware configuration. The password must
have a minimum of 8 characters by default, but this value
is configurable.
The user Administrator is predefined by default, but
you must create your own user name and password. For
security purposes, HP recommends that you delete the
Administrator user.
This user name and password are required to access the
console port with the telnet cp-nodename command.
AddUser
On
DHCP EnableDNS/DHCPNetwork
4. Select File → Exit to exit the Integrated Lights Out Setup Utility and resume the power-on
self-test.
5. Watch the screen carefully, and press the F9 key when prompted to access the ROM-Based
Setup Utility (RBSU).
Perform the following procedure for each HP ProLiant DL585 G2 node in the hardware
configuration:
1. For each node, make the settings listed in Table 3-4.
Table 3-4 RBSU Settings for HP ProLiant DL385 G2 Nodes
Set To This ValueOption NameMenu Name
Disabled
Embedded Serial PortSystem Options
COM1; IRQ4; IO: 3F8h-2FFh
Virtual Serial Port
On all nodes except the head node, set this value
to PXE boot
Embedded NICs/NIC 1 boot
Options
Disabled (head node only)
Embedded NICs/NIC 2 boot
Options
OS Control Mode
Power Regulator for
ProLiant
Set the following boot order on all nodes except
the head node:
• IPL:1 CD-ROM
• IPL:2 Floppy Drive (A:)
• IPL:3 USB Drive Key (C:)
• IPL:4 PCI Embedded HP NC373i
Multifunction Gigabit Adapter
• IPL:5 Hard Drive C:
Set the following boot order on the head node:
• IPL:1 CD-ROM
• IPL:2 Floppy Drive (A:)
• IPL:3 USB Drive Key (C:)
• IPL:4 Hard Drive C:
Standard Boot Order (IPL)
COM1; IRQ4; IO: 3F8h-3FFh
BIOS Serial Console PortBIOS Serial Console and
EMS
115200
BIOS Serial Console Baud
Rate
Disabled
EMS Console
32 Hardware Preparation