HP XC System Software Hardware Preparation Guide Version 2.1

iii. Change the BMC HTTP Service value from Disabled to Enabled.
6. From th e menus shown across the top of the Main window, choose Advanced ->
I/O Device Configuration, and change the value of Serial Port from SIO
COMM PORT to BMC COMM PORT.
_______________________ Note _______________________
As described in this step, you must change the value o f Serial Port
before proceeding to the next step.
7. From th e menus shown across the top of the Main window, choose Advanced ->
Console Redirection and do the following:
a. Change the Console Redirection value from Disabled to Enabled.
b. Change the Baud Rate value to 115.2K.
8. From the menus shown across the top of the Main window, choose Boot anddothe
following:
a. On the h ead node:
i. Set the boot order to this: CD-ROM, Removable Devices, Hard Drive.
ii. Disable PXE bo o ti ng by insert ing an exclamation point (!) at the beginning of
the following entries:
PXE MBA V7.7.2 Slot 0200
PXE MBA V7.7.2 Slot 0300
b. On compute nodes:
i. Set the boot order to this: CD-ROM, Removable Devices, PXE MBA
V7.7.2 Slot 0200, Hard Drive.
ii. Disable PXE bo o ti ng by insert ing an exclamation point (!) at the beginning of
the following entry:
PXE MBA V7.7.2 Slot 0300
9. From the menus shown across the top of the Main window, choose Power anddothe
following:
a. Change the Wake On Modem Ring value from Enabled to Disabled.
b. Change the Wake On LAN value from Enabled to Disabled.
10. From the Main menu of the BIO S, select the Exit -> Save Changes and Exit.
11. Repeat this procedure for every HP ProLiant DL145 G2 node in your XC system.
3.4.3 Preparing HP ProLiant DL385 and HP ProLiant DL585 Nodes
On HP ProLiant D L 385 and HP ProLiant DL585 servers, the appropriate settings are configured
using the foll owi ng tools:
Integrated Lights Out (iLO) Setup Utility
ROM-Based Setup Utility (RBSU)
Figure 3-6 shows the back of the HP ProLiant 385 server.
3-10 Preparing Individual Nodes