Hewlett-Packard HP SureStore E Disk System FC10 User and Service Guide

36(OHFWULFDO3UHSDUDWLRQ
Electrical Preparation
%HIRUHLQVWDOOLQJWKHGLVNV\VWHPPDNHVXUHWKHHQYLURQPHQWLVHTXLSSHGWRPHHW
SRZHUQHHGV
(OHFWULFDO5HTXLUHPHQWV
$OOHOHFWULFDOZLULQJWRWKHVHUYLFHSRLQWSOXJPXVWEHVL]HGWRFDUU\WKHIROORZLQJ
LQUXVKDQGVWHDG\VWDWHFXUUHQWV
Caution Multiple disk systems are not recommended on 110 V circuits. The
combined current drawn by multiple systems quickly exceeds 110-V
capacity.
7DEOH ,QUXVK6XUJH&XUUHQWDQG'XUDWLRQ
No. of Disk Systems
on Circuit Inrush Currents and Duration
1 Up to 20 amps for 10 to 12 milliseconds
2 Up to 40 amps for 10 to 12 milliseconds
3 Up to 60 amps for 10 to 12 milliseconds
4 Up to 80 amps for 10 to 12 milliseconds
7DEOH 0D[LPXP2SHUDWLQJ&XUUHQW
Incoming Voltage
AC RMS
Maximum RMS Current Drawn by One
Disk System
100 – 120 volts 5.3 – 6.5 amps
200 – 240 volts 2.6 – 3.2 amps