HP SureStore E Disk Array 12H User's and Service Manual (C5445-90901, September 1999)

Appendix D. Back-to-Back Racking
Installation Procedure
244
Racking
Table 21. Disk Array/Component Positioning
EIA Space
1
Component
2
Installed in
Front of Rack
Component
2
Installed in
Back of Rack
Rail - Clip Nut,
ear Standard,
Hole Position
1
Array Enclosure Flange -
Clip Nut,
ear Standard,
Hole Positions
1
2-meter Rack
1-13 Array #1 Array #4 3 7, 33
14 Filler PDU n/a n/a
15-27 Array #2 Array #5 45 49, 75
28-40 Array #3 Array #6 84 88, 114
41 Filler Air Scoop n/a n/a
1.6 Meter Rack
1-13 Array #1 Array #3 3 7, 33
14-26 Array #2 Array #4 42 46, 72
27-29 Filler/s Filler/s n/a n/a
30 Filler PDU n/a n/a
31 Filler Filler n/a n/a
32 Filler Air Scoop n/a n/a
1 – EIA spaces and holes are numbered from the bottom of the rack, up.
2 - Arrays are numbered from the bottom up beginning on the front of the rack, 1 through 3 (or 1
through 2), then from the back of the rack, bottom up 4 through 6 (or, 3 through 4).