HP SureStore E Disk Array FC60 Service Manual (A5635A)

A5635A Controller Enclosure Specifications 369
Reference / Legal /
Regulatory
AC Power:
AC Voltage and Frequency:
120 VAC (100 - 127 VAC), 50 to 60 Hz single phase
230 VAC (220 - 240 VAC), 50 to 60 Hz single phase
Auto-ranging
Current:
HP recommends the use of magnetic-type circuit breakers, which are capable of handling
large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately
for the steady state currents.
Power Consumption:
Heat Output:
615 BTU/hr.
Voltage Typical
Operating
Current
Maximum
Operating Current
In-Rush Current
100 - 127 VAC 1.5 A 2.3 A 21.7 A
220 - 240 VAC 0.8 A 1.2 A 42.9 A
Incoming Voltage
AC RMS Typical Power Consumption
100- 127 VAC 180 watts
200 - 240 VAC 180 watts