HP SureStore E Disk Array FC60 Service Manual (A5277A)

568&RQWUROOHU(QFORVXUH7URXEOHVKRRWLQJ
7URXEOHVKRRWLQJ
7DEOH 7URXEOHVKRRWLQJ%%83UREOHPV
Symptom Possible Cause Procedure
Fault-A or Fault-B LED
is on
A Left or right battery bank
has failed.
Replace the
BBU.
Full Charge-A or Full
Charge-B LED is off
A Left or right battery bank
is not yet fully charged.
Turn on the power and allow controller
module to operate for 7 hours to
recharge the batteries.
If after 7 hours, the battery low error
persists, replace the
BBU.
Full Charge-A and Full
Charge-B LEDs are
flashing
A Batteries are charging The batteries should fully charge in 7
hours. If the BBU is not fully charged in 7
hours, replace the BBU.
“Battery Low” error
issued by software
A Power turned off for
extended period and
drained battery power.
Turn on the power and allow controller
module to operate for 7 hours to
recharge the batteries.
If after 7 hours, the battery low error
persists, replace the
BBU.
B Batteries are weak and
BBU is due for
replacement.
Check the last service date for the
BBU.
Operation in an environment with
elevated temperature (above 35
º
C or 95
º
F) may reduce the life expectancy of the
BBU to as low as 6 months.
New
BBU will not hold
a charge
A Battery charger board
failure
Replace the BBU.
Allow the system to operate for at least 7
hours in order to properly charge the
batteries. If this does not solve the
problem, go to cause B.
B Faulty battery harness Replace both power supplies.
Replace the battery harness.
Loss of battery backup
during a power outage
A Battery failure. Replace the BBU.