HP StoreEver MSL6480 Tape Library User and Service Guide
Table 22 Warning events (continued)
Details and solutionMessage and descriptionEvent code
operation with a different cartridge in the same
drive.
2. Check the library event log for events associated
with this drive.
3. Use the RMI to pull a drive support ticket and
check the device analysis section for more
information. Use L&TT to view the support ticket.
Library test failed due to a drive issue.4014 1. Verify the test parameters and then retry the test.
2. Check the library event log for events associated
with this drive.
3. Use the RMI to pull a drive support ticket and
check the device analysis section for more
information. Use L&TT to view the support ticket.
Power supply has failed. Redundancy is not
available.
4015 1. Verify that each module has two power supplies
installed.
2. Ensure that all power supplies are installed
properly.
3. Verify that all power sources are supplying
power that is within the product requirements.
Restore configuration data from chassis failed.4017 1. If possible, save the library configuration to a
file.
2. Power cycle the library and retry the operation.
Firmware upgrade of one or more drives failed due
to drive issue.
4018 1. Verify that the firmware file is correct for the
drive.
2. Ensure that the drive is in a healthy state and
does not have a cartridge.
General drive firmware bundle upgrade failure.4019
3. Retry the operation.
Restore previously saved configuration data. If you
don’t have a saved configuration file, reconfigure
the library.
Database has been reset due to a problem that
prevented the library from powering up.
4020
Reinsert the removed drive in the same position from
which it was removed.
Drive has been hot removed while in active status
as data transfer device. Drives must be powered
off before removing them from the library.
4021
Reinstall the tape drive in an acceptable location.A full-height drive in incorrect boundary location.
Full-height drives will only operate in the very top,
4022
very bottom, or middle pair of half-height drive
bays.
The tape drive must have an FC or SAS cable
attached to transfer data and communicate with
host applications.
Drive not cabled (ports not linked up).4023
Library test failed due to a cartridge error.4025 1. Remove the cartridge and inspect it for damage.
2. Retry the operation with another cartridge.
The library does not support use of unlabeled
media. Remove any unlabeled cartridges from the
Unlabeled media detected in library.4026
library and verify that all cartridges have
high-quality proper barcode labels, as specified in
“Labeling tape cartridges” (page 15).
Drive cannot use this media due to it being an
unknown or unsupported format. Possibly the media
the wrong generation of media.
4028 1. Verify that the LTO generation on the barcode
label media ID matches the LTO generation of
the tape cartridge.
2. Remove cartridges that are incompatible with
the drives in the library.
161